AWT420 Transmitter
Overview
The AWT420 transmitter can be used with either analog or digital EZLink sensors for a wide range of applications including drinking water, wastewater, industrial water and power.
Operation simplicity is a key feature of the AWT420 with its powerful, yet intuitive software, advanced self-diagnostics and its unique modular design that enables users to achieve increased efficiency through greater user flexibility, reduced process downtime and simplified maintenance.
With integrated Bluetooth you can securely connect to any iOS or Android device using the EZLink connect app to easily access essential sensor information. From checking your audit logs to downloading the latest software through your smartphone, we are confident that EZLink connect will make your life that little bit easier by providing you with a wealth of information and services to support you wherever and whenever you need it.
- Plug-and-play universal modular design
- 'Easy Setup' menus provide step-by-step guidance
- Multi-level security access prevents unauthorized modification of process control data
- Secure data archiving to an SD card
- Direct connection to your smart device
- HART, Ethernet, PROFIBUS or MODBUS digital communications
- Wall-, panel- or pipe-mountable
Data
Operation
- Number of sensor inputs
- Up to 2 analog or digital sensors
- Measurement parameters
- pH/ORP, 2-electrode conductivity, 4-electrode conductivity, optical dissolved oxygen, turbidity/suspended solids
- Language
- English, German, Italian, Spanish, French, Portuguese, Russian, Turkish, Polish, Chinese
Mechanical data
- Protection:
- IP66 / NEMA 4X
- Dimensions:
- 144 × 144 × 99 mm (5.67 × 5.67 × 3.89 in)
- Weight
- Aluminium enclosure: 1.364 kg (2.5 lb)
- Polycarbonate enclosure: 1.0 kg (2.2 lb)
Electrical
- Supply voltage
- 100 to 240 V AC ±10 %, 50/60 Hz
- 24 V DC (18 min. to 36 max.)
- Power consumption
- <15W
Analog outputs
- 2 standard + 2 optional with analog module
Relay outputs
- 4 standard
Digital input/output
- 1 standard, user-programmable as input or output
Connectivity/Communications (optional)
- Ethernet
- PROFIBUS DP
- MODBUS RTU RS485
- HART
Hazardous area approvals (aluminium enclosure only)
- Hazloc EZLink channels fitted:
- ATEX/IECEx
- II 3(3) G Ex ic ec NC [ic Gc] IIC T4 Gc
- – 10 ⁰C </ Ta </ + 45 ⁰C, IP66
- cULus
- Class I, Div 2, Gps ABCD T4
- – 10 ⁰C </ Ta </ + 45 ⁰C, IP66
- No Hazloc EZLink channels fitted:
- ATEX/IECEx
- II 3 G Ex ice c Nc IIC T4 Gc
- – 10 ⁰C </ Ta </ + 45 ⁰C, IP66
- cULus
- Class I, Div 2, Gps ABCD T4
- – 10 ⁰C </ Ta </ + 45 ⁰C, IP66
Marine Approval
- Lloyd's Register approved for marine applications (category ENV2)
- Tested according to IACS UR E10, Rev. 7, Oct. 2018
MCERTS
Certificate no. Sira MC220375/00